The Cat® EMCP 4 Control Panel provides all of the controls and system indicators in one easy to access interface.
Standard Equipment:
-
- Control
-
- Auto / Start / Stop control
- Remote start / stop
- Speed and voltage adjust
- Engine Cooldown Timer
- Local and remote emergency stop
- Engine Cycle Crank
- Programmable Cycle Timer
-
- Display
-
- A 480 x 320 pixel, 5.5 inch, white backlit graphical display denotes text alarm/event descriptions, set points, engine and generator monitoring, and is visible in all lighting conditions.
-
- Generator Monitoring
-
- Voltage (L-L, L-N)
- Current (Phase)
- Average Volt, Amp, Frequency
- kW, kVAr, kVA (Average, Phase, %)
- Power Factor (Average, Phase)
- kW-hr, kVAr-hr (total)
-
- Generator Protection
-
- Over/Under voltage (27/59)
- Over/Under frequency (81/OU)
- Generator phase sequence
- Overcurrent (50/51)
- Overcurrent (Thermal Damage Curve)
- Reverse Power (kW)(32)
- Reverse Reactive Power (kVAr) (32RV)
- Current Balance (46)
-
- Engine Monitoring
-
- Engine speed (RPM)
- Battery voltage
- Oil pressure
- Oil Temperature
- Coolant temperature
- Multiple Language Support
- Crank attempt and successful start counter
- Run hours
- Enhanced engine monitoring (with electronic engines)
-
- Engine Protection
-
- Low engine oil pressure (alarm)
- High engine oil temp (alarm and shutdown)
- High coolant temp (alarm and shutdown)
- Low coolant temp (alarm)
- Low coolant level (alarm)
- Overcrank
- Overspeed
- Control switch not in auto (alarm)
- Low, high, and weak battery voltage
-
- Communications
-
- Primary and accessory CAN data links
- RS-485 annunciator data link
- Modbus RTU (RS-485 Half duplex)
- Modbus TCP (10BT Ethernet)
-
- Inputs & Outputs
-
- Sixteen programmable digital outputs
- Two dedicated analog inputs
- One programmable analog input
- Two dedicated digital inputs
- Twelve programmable digital inputs
-
- Language Support
-
- Arabic, Bulgarian, Chinese, Czech, Danish, Dutch, English, Estonian, Finnish, French, German, Greek, Hungarian, Icelandic, Italian, Latvian, Lithuanian, Japanese, Norwgian, Polish, Portguese, Romanian, Russian, Slovak, Slovene, Spanish, Swedish & Turkish
-
- Environmental
-
- Control module operating temperature: -40°C to 70°C
- Display operating temperature: -20°C to 70°C
- Humidity: 100% condensing 30°C to 60°C
- Storage temperature: -40°C to 85°C
- Vibration: Random profile, 24-1000 Hz, 6.0G ms
Optional Equipment:
-
- Generator Monitoring
-
- Excitation voltage and current (with CDVR)
- Generator stator and bearing temp (with optional module)
-
- Can Annunciator
-
- The EMCP 4 CAN Annunciator serves to display genset system alarm conditions and status indications.The annunciator has been designed for use on the accessory communication network and may be used in either local (package mounted) or remote (up to 800 feet) application.
- A maximum of four annunciators may be used with a single EMCP 4.3
-
- Rs-485 Annunciator
-
- The EMCP 4 RS-485 Annunciator serves to display genset system alarm conditions and status indications.The annunciator has been designed for use on the long distance annunciator datalink and is used for remote (up to 4000 feet) application.
-
- Remote Hmi Display
-
- The EMCP 4 Remote HMI serves to display generator set system alarm conditions and status indications through an interactive graphical interface. Featuring an 8 inch color LCD touch screen that may be mounted remotely using 1m harness with terminal block. A maximum of 1 display may be used with a single EMCP 4.3.
-
- Remote Monitoring Software
-
- The EMCP 4 remote monitoring software package is a PC based program which allows the user tomonitor and control a generator set, and is capable of running on a Windows based operating system.The remote monitoring software allows the user to configure data monitoring and data acquisitionprocesses for monitoring, graphing, and logging of genset data.
-
- Digital Input/output Module
-
- The Digital Input/Output (DI/O) module serves to provide expandable Input and Output capability of the EMCP 4 and is capable of reading 12 digitalinputs and setting 8 relay outputs. The DI/Omodule has been designed for use on the accessoryCommunication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.
- A maximum of four DI/O modules may be used with a single EMCP 4.3.
-
- Rtd Module
-
- The RTD module serves to provide expandable generator temperature monitoring capability of the EMCP 4 and is capable of reading up to eight type 2-wire, 3-wire and 4-wire RTD inputs. The RTD Module has been designed for use on the Accessory Communication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.
- A maximum of one RTD Module may be used with a single EMCP 4.3.
-
- Thermocouple Module
-
- The thermocouple module serves to provide expandable engine and generator temperature monitoring capability of the EMCP 4 and iscapable of reading up to twenty Type J or K thermocouple inputs. The thermocouple module has been designed for use on the accessory communication Network and may be used in either local (package mounted) or remote (up to 800 feet) application.
- A maximum of one thermocouple module may be used with a single EMCP 4.3 on each datalink.
G3520H Gas Generator
- Continuous Rating
- 2519 / 2500 ekW @ 1.0pf
- Fuel Type
- Natural Gas, Hydrogen Blend (up to 25%)
- Maximum Electrical Efficiency
- 45.30%
G3520C Gas Generator
- Continuous Rating
- 2050 ekW
- Fuel Type
- Natural Gas, Biogas, Coal Gas
- Maximum Electrical Efficiency
- 40.10%
Gas Generator G3516H
- Continuous Rating
- 2027 / 2007 ekW @ 1.0pf
- Fuel Type
- Natural Gas, Hydrogen Blend (up to 25%)
- Maximum Electrical Efficiency
- 45.30%
G3516C Gas Generator Set
- Continuous Rating
- 1660 ekW
- Fuel Type
- Natural Gas
- Maximum Electrical Efficiency
- 37.70%
G3512E Gas Generator Set
- Continuous Rating
- 1200 ekW
- Fuel Type
- Natural Gas
- Maximum Electrical Efficiency
- 42.30%
Gas Generator G3512H
- Continuous Rating
- 1515 ekW / 1505 ekW @1.0pf
- Fuel Type
- Natural Gas, Hydrogen Blend (up to 25%)
- Maximum Electrical Efficiency
- 44.90%
C175-20
- Standby Rating
- 4000 (no fan)/3900/3620(no fan)/3500 ekW
- Prime Power Rating
- 3600 (no fan)/3500/3300 (no fan)/3180 ekW
- Emissions/Fuel Strategy
- Low Fuel, Tier 2
C175-16 Tier 4 Final
- Standby Rating
- 3100(no fan)/3000 ekW
- Prime Power Rating
- 2825(no fan)/2725 ekW
- Emissions/Fuel Strategy
- U.S. EPA Certified Tier 4
C175-16 Generator Set
- Standby Rating
- 3365(no fan)/3250/3100(no fan)/3000 ekW
- Prime Power Rating
- 3115(no fan)/3000/2825(no fan)/2725 ekW
- Emissions/Fuel Strategy
- Low Fuel, Tier 2
3516E Low Voltage Generator Set
- Standby Rating
- 3000 ekW
- Prime Power Rating
- 2725 ekW
- Emissions/Fuel Strategy
- Tier 2
3516C Generator Set
- Standby Rating
- 2500/2250/2000 ekW
- Prime Power Rating
- 2250/2045/1825 ekW
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 2
3516C Tier 4 Final
- Standby Rating
- 2500/2000 ekW
- Prime Power Rating
- 1825/2250 ekW
- Emissions/Fuel Strategy
- U.S. EPA Certified
3512C Generator Set
- Standby Rating
- 1750 ekW
- Prime Power Rating
- 1600 ekW
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 2
3516 Diesel Generator Set
- Standby Rating
- 1750 ekW
- Prime Power Rating
- 1600 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption
3512C Generator Set
- Standby Rating
- 1500 ekW
- Prime Power Rating
- 1360 ekW
- Emissions/Fuel Strategy
- U.S. EPA Certified
3512 with Upgradeable Package
- Standby Rating
- 1250/1100 ekW
- Prime Power Rating
- 1135/1000 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption
C32 (60 Hz)
- Maximum Rating
- 1250 ekW
- Minimum Rating
- 830 ekW
- Emissions/Fuel Strategy
- Low Fuel, Tier 2 Nonroad Stds
C27 Generator Set
- Maximum Rating
- 800 ekW
- Minimum Rating
- 635 ekW
- Emissions/Fuel Strategy
- Low Fuel, Tier 2 Nonroad Equivalent
C175-20
- Standby Rating
- 4000(no fan)/3900 kVA
- Prime Power Rating
- 3600(no fan)/3500 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
C175-16 Generator Set
- Standby Rating
- 3100(no fan)/3000 kVA
- Prime Power Rating
- 2825(no fan)/2725 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516E Generator Set
- Maximum Rating
- 3500 kVA
- Minimum Rating
- 3000 kVA
- Emissions/Fuel Strategy
- Tier 2 Equivalent - 1808 rpm
3516E Low Voltage Generator Set
- Standby Rating
- 3000 kVA (3100 kVA without fan)
- Prime Power Rating
- 2750 kVA (2850 kVA without fan)
- Emissions/Fuel Strategy
- Low Fuel Consumption
3516C Generator Set
- Maximum Rating
- 3125 kVA
- Minimum Rating
- 2250 kVA
- Emissions/Fuel Strategy
- U.S. EPA Cert., Tier 2 - 1808 rpm
3516C (50 Hz) with Upgradeable Package
- Standby Rating
- 2750 kVA
- Prime Power Rating
- 2500 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3516C Generator Set
- Standby Rating
- 2750 kVA
- Prime Power Rating
- 2500 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516B (60 Hz) with Upgradeable Package
- Standby Rating
- 2250 ekW
- Prime Power Rating
- 1825 ekW
- Emissions/Fuel Strategy
- Low fuel, Low Emissions
3516B Generator Set
- Standby Rating
- 2250 ekW
- Prime Power Rating
- 1825 ekW
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516B Generator Set
- Standby Rating
- 2500 kVA
- Prime Power Rating
- 2275 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516B (50 Hz) Generator Set
- Standby Rating
- 2500 kVA
- Prime Power Rating
- 2275 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516B Generator Set
- Prime Power Rating
- 1825 ekW
- Continuous Rating
- 1640 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption
3516B Generator Set
- Prime Power Rating
- 2275/2000 kVA
- Continuous Rating
- 2000/1750 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3516B Generator Set
- Standby Rating
- 2250 kVA
- Prime Power Rating
- 2000 kVA
- Emissions/Fuel Strategy
- Low fuel, Low Emissions
3516B Generator Set
- Standby Rating
- 2250 kVA
- Prime Power Rating
- 2000 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3516B (50 Hz) India Market Only
- Maximum Rating
- 2250 kVA
- Minimum Rating
- 2000 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3516 Diesel Generator Set
- Standby Rating
- 2000 kVA
- Prime Power Rating
- 1825 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3512B Diesel Generator Set
- Standby Rating
- 1500/1400 kW
- Prime Power Rating
- 1360/1275 kW
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3512B Diesel Generator Set
- Standby Rating
- 1500/1400 ekW
- Prime Power Rating
- 1360/1275 ekW
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3512B Diesel Generator Set
- Standby Rating
- 1875/1750/1625/1500 kVA
- Prime Power Rating
- 1700/1600/1500/1360 kVA
- Emissions/Fuel Strategy
- Low Fuel , Low Emissions
3512B (50 Hz) Generator Set
- Standby Rating
- 1875/1750/1600/1500 kVA
- Prime Power Rating
- 1700/1600/1500/1360 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
3512B (50 Hz) India Market Only
- Maximum Rating
- 1500 kVA
- Minimum Rating
- 1500 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3512 Generator Set
- Standby Rating
- 1400/1250 kVA
- Prime Power Rating
- 1275/1150 kVA
- Emissions/Fuel Strategy
- Low fuel, Low Emissions
C32 Generator Set
- Maximum Rating
- 1500 kVA
- Minimum Rating
- 910 kVA
- Emissions/Fuel Strategy
- Low Fuel, Low Emissions
C32 (50 Hz) India Market Only
- Maximum Rating
- 1250 kVA
- Minimum Rating
- 1010 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3412C Generator Set
- Maximum Rating
- 900 kVA
- Minimum Rating
- 680 kVA
- Emissions/Fuel Strategy
- Low Fuel Consumption
3412C Generator Set
- Maximum Rating
- 800 ekW
- Minimum Rating
- 635 ekW
- Emissions/Fuel Strategy
- Low Fuel Consumption