fbpx

C13 Generator Set

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

Maximum Rating
400 ekW
Minimum Rating
320 ekW
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts

Generator Set Specifications

Maximum Rating
400 ekW
Minimum Rating
320 ekW
Emissions/Fuel Strategy
Low Fuel Consumption
Voltage
380 to 415 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime

Engine Specifications

Engine Model
C13 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
5.12in
Stroke
6.18in
Displacement
762.8in³
Compression Ratio
16.3:1
Aspiration
Air to Air Aftercooled
Fuel System
MEUI
Governor Type
Adem™A4

Generator Set Dimensions

Length - Maximum
186.7in
Width - Maximum
79.3in
Height - Maximum
84in

Standard Equipment:

  • Air Inlet System
    • Aftercooler core
    • Air cleaner; light duty with disposable paper filter
    • Turbocharger
  • Control Panel
    • GCCP 1.3
  • Cooling System
    • Caterpillar extended life coolant
    • Coolant drain line with valve
    • Fan drive, battery charging alternator drive
    • Radiator and cooling fan with guard
  • Exhaust System
    • Stainless steel exhaust flex, gaskets, raincap & SAE exhaust flange for customer use - shipped loose
  • Fuel System
    • Base, formed steel with single wall integral 8-hour fuel tank
    • Standard open set fuel tank/base supplied
  • Generator And Attachments
    • Segregated low voltage (AC/DC) wiring panel
    • Power center, IP22
    • Integrated voltage regulator (IVR)
    • Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
    • A Frame generator - IP21 Protection
    • Optional LC Frame generator - IP23 Protection
  • Governing System
    • Cat electronic governor (ADEM A4)
  • Packaged Generator Set
    • Service indicator
    • Radiator package mounted
    • Low coolant level sensor
    • Coolant drain line with valve
    • Coolant level sight gauge
    • Disposable air filter
  • Lube System
    • Lubricating oil
    • Oil drain valves
    • Oil cooler
  • Mounting System
    • Captive linear vibration isolators between base and engine-generator
    • Includes lifting provisions and termination points for coolant and lube oil drain lines
  • Starting / Charging System
    • 24V battery with rack and cables
  • General
    • Engine and alternator pre-paint, Caterpillar yellow

Optional Equipment:

  • European Certificates
    • EU Certificate of Conformance (CE)
    • Global Certification for CIS
  • Air Inlet System
    • Single element air cleaner
    • Dual element air cleaner
  • Circuit Breakers
    • 4 Pole (IEC-100% rated) Circuit breaker
    • Circuit breaker (IEC) Auxiliary contacts
    • 4 Pole (IEC-100% rated) Circuit breaker - Motorised
    • Padlockable circuit breaker device
    • Power terminal strip
    • Shunt trip for IEC circuit breaker
    • 3 Pole (IEC-100% rated) Circuit breaker
    • 3 Pole (IEC-100% rated) Circuit breakers - Motorised
  • Control Panels
    • GCCP 1.4
    • Local alarm modules: Local annunciator
    • Volt free contacts
    • Control panel protective devices: Earth fault relay ; Earth leakage ground fault ; Overload shutdown via breaker ; Low fuel level alarm ; Low fuel level shutdown ; High fuel level alarm ; Fuel level sensor
    • Remote annunciator module
  • Cooling System
    • Stone guards
    • Radiator duct flange
    • Low coolant temperature alarm
  • Enclosures
    • Sound attenuated enclosures
    • High ambient sound attenuated enclosures
  • Exhaust System
    • 6 and 8 inch elbow kit
    • Flexible 8 inch exhaust fittings
    • 6 and 8 inch flange GP
    • Mufflers - End in/end out
    • 10, 25 and 35 dBA attenuation
  • Fuel System
    • Manual fuel transfer pump
    • Integral dual wall fuel tank base
    • Fuel transfer system controls
  • Generator And Attachments
    • Permanent magnet excitation (PMG) generator
    • LC frame generator
    • LC CIP generator
    • A Frame CIP generator
    • A Frame oversize generator
    • Ingress protection
    • Space heaters
  • Lube System
    • Manual sump pump
  • Mounting System
    • Narrow skid base
  • Starting / Charging System
    • 5 Amp single Battery charger
    • Jacket water heater
    • Battery disconnect switch

C13, C15, C18 SA enclosure. 350-600 kW 60 Hz

Length
C13 - 5461 mm, C15 - 4948 mm, C18 - 5187 mm
Width
C13, C15 & C18 - 2014 mm
Height
C13 - 2743 mm, C15 - 2619 mm, C18 - 2561 mm

C13, C15, C18 WP Enclosure. 350-600 kW 60 Hz

Height
2320 - 3209 mm
Length
4948 - 7271 mm
Width
2014 - 2056 mm

C13 Sound Attenuated Enclosure 50 and 60 Hz

Length
4930 mm
Height
2221 mm
Width
1620 mm

Emergency Transfer Load manager

Configuration
Wall mounted paralleling control system that monitors and controls a single generator and a single utility.
Modes of Operation
Utility Import, Export, and base load operations, Peak shaving, and Emergency Standby. Closed Transition to/from Generator Power
Application
LV and MV (208V-32kV)

Specifications

Standard/Optional Features

Attachments